Chemical Dosing System

 

ELECTRONIC PUMPS 

All the electronic pumps possess microprocessor technology. The pump is continuously measuring a voltage, which in turn determines the mode of operation, within the hydraulic preset characteristics of it.

There are three series of electronic pumps, namely the F, G and C series.

"F" series electronic pumps are designed to inject small volume of chemicals accurately; (0.03L/hr to 10L/hr).

"G" series electronic pumps are designed to inject chemicals accurately from 1.0L/hr to 30L/hr.

"C" series electronic pumps are suitable to inject chemicals accurately within 20L  to 60L/hr.

Please refer to following pictures:

"F" series wall mounted analog pump "F" series wall mounted digital pump
"G" series wall mounted analog pump "G" series wall mounted digital pump
"C" series foot mounted analog pump "C" series foot mounted digital pump

 

Each series of pump has different models for various types of application.

The models available in analog pumps are :

Model Main features and characteristics
CO Constant flow, On/Off mode; injection frequency adjustment 0-100%
CL Same as CO mode with additional level control and level switch with coaxial cable.
PV

Proportional mode divider (1:n) to external voltage free contact (turndown ratio 1-1000)

PVM

In addition to the PV model, step-up mode (multiplier, 1xn) and divider mode (turndown ratio 1-1000)

IC Proportional response to an external analog signal: avalable at 0-20mA or 4-20 mA.
TE

Timer pump with start-up signals, not available in C series

CE Constant flow, On/Off mode; injection frequency adjustment 0-100%, only available in F series

The models available for digital pumps are :

Model Main features and characteristics
MAN constant flow, level control, stroke frequency % rate, stroke/min, stroke/hour.
EXT proportional mode to external mA, mV or V signal; proportional mode divider (1:n) and multiplier (1xn) of external pulses without pacer.
EXT RS-485 same as EXT, in addition RS 485 connection for remote control.
RH driven by built in redox meter (mV) proportionally.
CD

driven by built in conductivity meter; proportional mode, only available in F series.

EN

with internal weekly timer, eight daily programs, only available in F series.

PH driven by built in ph meter proportionally.

 

© 2001 Hydroventure Sdn Bhd. All rights reserved.